Knowledge/Calculators and tables/Evaporative airflow and relief air, checked two ways

Evaporative airflow and relief air, checked two ways

Divide the cooler's airflow by the room volume to get air changes per hour (ACH). Aim for at least 20 and no more than about 40, with 30 as the trade shortcut. Then check the relief path. Each room needs an exhaust opening about twice its vent area, and the door test and the tissue test prove it.

Air changes (ACH)
airflow ÷ volumem³/h divided by m³
From L/s
× 3.6 ÷ volumevolume in m³
Target range
20 to 40 ACH30 is the shortcut
Relief opening
2 × vent areaper room

How do you work out air changes per hour?

  • ACH = cooler airflow in m³/h, divided by the space volume in m³
  • Or ACH = cooler airflow in L/s, times 3.6, divided by the space volume in m³
  • Space volume = floor area in m², times ceiling height in m

So a 200 m² house with 2.7 m ceilings is 540 m³. A cooler delivering 4,500 L/s gives 16,200 m³/h, and 16,200 divided by 540 is 30 air changes an hour. The Commonwealth research uses this same house and cooler as its example. It's a handy check when a supplier's sizing looks wrong.

Commonwealth technical research on evaporative air conditioners. The design range from AIRAH, the Australian Institute of Refrigeration, Air Conditioning and Heating, is at least 20 ACH with a maximum of about 40.
HouseCeilingVolumeAirflow for 30 ACH
130 m²2.4 m312 m³9,360 m³/h, or 2,600 L/s
200 m²2.7 m540 m³16,200 m³/h, or 4,500 L/s

Which airflow figure should you size from?

Use the airflow figure at 80 Pa external static, the resistance the fan pushes against once it's ducted. That's roughly what an evaporative fan is specified against. The big airflow number on the brochure isn't that figure.

And the outlets have to be able to pass it. Seeley's rule, word for word, is "total outlet airflow must be greater than or equal to cooler airflow at 80 Pa."

Seeley International. A 2,600 L/s cooler wants roughly seven or eight 400 mm outlets to pass its own airflow.
Outlet sizeCapacity
350 mm250 to 300 L/s
400 mm350 to 400 L/s
450 mm450 to 500 L/s

How do you prove the relief air is enough?

Sizing the cooler and the outlets gets air into the house. Relief air is what lets it out, and without it the rest doesn't work.

Give every room an exhaust opening about twice the vent size. Open the windows or doors furthest from the vents. Then prove it with two tests that cost nothing.

  1. The door testAt high fan speed, a door should stay slightly ajar without slamming shut. If it slams, the room is pressurising.
  2. The tissue paper testA piece of tissue paper shouldn't stick to the fly screen while the unit runs. If it sticks, air is trying to leave faster than the opening allows.

There's no published Australian rule for relief air along the lines of "this much opening for this much airflow". We looked. If somebody quotes you a tidy square-metres-per-litre-per-second ratio, ask them for the source, because we couldn't find one.

Want a second opinion on a number?

Calculators are only as good as the assumptions under them, and the assumptions are where jobs go wrong.

If a figure looks off against what you see on site, that instinct is usually worth more than the calculator. Ask Kevin.

Who this is for: small and medium HVAC contractors in Victoria. If you're a homeowner after a rebate or a repair, you need a licensed contractor, not us, and yours can point you the right way.

Have a chat with Kevin

Kevin reads every one of these himself and calls back. No newsletter, no sales sequence.

Or call Kevin on 0408 624486

Review date: 1 April 2027. Figures in this area change without much notice and this page carries some that will go stale. Every number above is dated and sourced so you can check it yourself. If you find something out of date here, tell us and we will fix it.