The conversions that come up on Australian HVAC work

Five come up often enough to keep handy. Airflow per kW, air changes per hour (ACH), m³/h against L/s, electrical conductivity (EC) to total dissolved solids (TDS), and ozone depletion potential (ODP) tonnes to refrigerant mass. Each one says where it came from, because a conversion factor without a source is just a number.

Airflow
54 L/s per kWflagged unverified, see below
Air changes
L/s × 3.6 ÷ m³gives ACH
Water quality
TDS = EC × 0.6mg/L from µS/cm
Airflow units
1 L/s = 3.6 m³/hexact

Which conversions come up, and where does each one come from?

A worked pair to check the airflow conversions against. 9,360 m³/h equals 2,600 L/s, and 16,200 m³/h equals 4,500 L/s.
ConvertFactorSource and confidence
Litres per second to cubic metres per hour× 3.6Exact, by definition
Airflow to air changes per hourACH = L/s × 3.6 ÷ volume in m³AIRAH (Australian Institute of Refrigeration, Air Conditioning and Heating) Skills Workshop Module 48
Electrical conductivity to total dissolved solidsTDS in mg/L = EC in µS/cm × 0.6Commonwealth evaporative air conditioner research
Airflow per kW of capacityAbout 54 L/s per kWFlagged unverified in our own research. Use a manufacturer figure
ODP tonnes to HCFC-22 mass1 ODP tonne is about 18 tonnes of HCFC-22, which is R22Derived from the scheduled ODP value of 0.055

Watch the fourth row. 54 L/s per kW is flagged unverified in our own research. Airflow per kW changes with the system type, the temperature difference and the static. If it matters, use the design airflow from the unit's data, not a rule of thumb.

Which of the four pressure units goes where?

  • 1 bar = 100 kPa = 0.1 MPa
  • 1 kPa = 1,000 Pa
  • Evaporative fans are specified at roughly 80 Pa external static
  • Gas ducted pressure switches close at 55 Pa and 18 Pa
  • Refrigerant pressures are usually quoted in bar gauge (barg), and R744, which is CO2, reaches about 63 barg at 25°C

Duct static is measured in Pa and refrigerant in bar, and one bar is 100,000 Pa. Mix them up and you put the wrong gauge on the job.

Left out on purpose

Why there's no kW to BTU (British thermal unit) factor here

It's the conversion people expect on a page like this, and we've left it out on purpose. No BTU conversion factor turned up anywhere in our sourced research, so publishing one would mean pulling a number from memory.

Yes, that's a bit silly for such a well-known conversion. But we'd rather say so than slip in a number we can't back up. Every figure on this page comes from something we actually read.

In practice Australian equipment is rated and registered in kW, the GEMS register (Greenhouse and Energy Minimum Standards) works in kW, and the Victorian Energy Upgrades (VEU) categories are defined in kW. If you're being quoted in BTU, you're probably reading imported marketing material, which is worth noticing in itself.

Something here you would use more of?

These pages exist because somebody needed the number and could not find it quickly. If there is one missing, that is worth knowing.

Tell Kevin what you went looking for.

Who this is for: small and medium HVAC contractors in Victoria. If you're a homeowner after a rebate or a repair, you need a licensed contractor, not us, and yours can point you the right way.

Have a chat with Kevin

Kevin reads every one of these himself and calls back. No newsletter, no sales sequence.

Or call Kevin on 0408 624486

Review date: 1 April 2027. Figures in this area change without much notice and this page carries some that will go stale. Every number above is dated and sourced so you can check it yourself. If you find something out of date here, tell us and we will fix it.