Knowledge/Gas safety and CO/Every open-flued space heater under a Victorian alert

Every open-flued space heater under a Victorian alert

Six heater families are under a current Energy Safe Victoria alert. They're Vulcan and Pyrox Heritage, Regency i31, Nectre 2000, Real Flame Pyrotech, Regency F38 and FG38, and Cannon Fitzroy and Canterbury. On five of them you service as normal and add a negative pressure and carbon monoxide (CO) spillage check. On the Heritage you isolate it instead.

Heater families on alert
6all open-flued space heaters
The exception
Heritageisolate it, don't service it
Sales ban from
1 Aug 2022unless it meets the new standards
Deaths since 2010
3CO from open-flued gas space heaters

Which heaters are on the list?

Energy Safe Victoria safety alerts. The Regency F38 and FG38 were Masport-branded before 2006, and the LP model isn't covered. Cannon Fitzroy and Canterbury covers 2001 to 2009.
HeaterSupplierContact
Vulcan and Pyrox HeritageClimate Technologies03 8795 2462
Regency i31, from 2010Fireplace Products Australia1800 860 660
Nectre 2000, from 2007Glen Dimplex1300 014 389
Real Flame Pyrotech, from 2012Glen Dimplex1300 014 389
Regency F38 and FG38Fireplace Products Australia1800 860 660
Cannon Fitzroy and CanterburySampford IXL1800 035 410

Every one of them is an open-flued gas space heater. None of them is a ducted heater, and that distinction matters more than it looks.

Why is the Heritage handled differently?

GIS 59, one of Energy Safe Victoria's (ESV) gas information sheets, has one rule for these heaters and one exception. For every heater except the Heritage, service it as normal and add a check for negative pressure and CO spillage.

For the Heritage, isolate the appliance. Tell the customer to contact Climate Technologies or the Department of Health and Human Services (the name GIS 59 uses), whichever fits. Don't service it and hand it back.

The recall and the alert are two different things

The Heritage matter usually gets described as one event, and it's two. The recall of 3 June 2009 by the Australian Competition and Consumer Commission (ACCC) was narrow. It covered Climate Technologies models 4804BN, 4804SB, 4808SB and 4808BN, serials 00706981 to 00794271, sold between 1 August 2007 and 28 May 2008. The reason was incorrect burner assembly, which could cause unacceptable CO emission levels.

The ESV safety alert and deed of undertaking (a formal, legally binding promise) is far wider and still current. It reaches heaters first manufactured in 1977. All were withdrawn from sale, manufacture stopped, and Climate Technologies ran a testing program with a $150 rebate toward a gasfitter inspection. Residents must not use them until a qualified gasfitter has serviced them.

Myth
we
checked

There's no Brivis or Braemar gas ducted recall

You'll hear there's a recall on Brivis or Braemar ducted heaters over cracked heat exchangers. We went looking for it. There's no Brivis or Braemar gas ducted heater recall and no Energy Safe alert against either.

Cracked heat exchangers are a well-documented failure on those units, and trade forums talk about them a lot. But a known fault isn't a recall. Every current Victorian alert and recall in this space is for an open-flued space heater.

It matters because telling a customer their heater is under a recall when it isn't is a claim you'd have to stand behind. Find the fault, document the fault, quote the fault.

What did the 2022 ban actually stop?

Since 1 August 2022, some open-flued gas space heaters can't be sold or supplied in Victoria unless they meet the updated Australian and New Zealand safety standards, AS/NZS 5263.1.3 and AS/NZS 5263.1.8.

The ban is about what the heater does, not which model it is. It catches any open-flued space heater that doesn't shut itself down within 15 minutes if combustion products spill under any negative pressure condition. Heaters installed before 1 August 2022 are grandfathered, so the ban doesn't touch them.

And the reason it exists is worth knowing when a customer pushes back. The ban follows a recommendation by the Victorian Coroner that these appliances be phased out.

Found something on site you're not sure about?

Gas safety is the one area where the right answer and the comfortable answer aren't always the same, and you're the one holding the licence.

If you've got a job you're weighing up, Kevin's happy to talk it through.

Who this is for: small and medium HVAC contractors in Victoria. If you're a homeowner after a rebate or a repair, you need a licensed contractor, not us, and yours can point you the right way.

Have a chat with Kevin

Kevin reads every one of these himself and calls back. No newsletter, no sales sequence.

Or call Kevin on 0408 624486

Review date: 1 March 2027. Figures in this area change without much notice and this page carries some that will go stale. Every number above is dated and sourced so you can check it yourself. If you find something out of date here, tell us and we will fix it.